Control, operation and Supervisory Integrated Controllers
- Realizes high-speed advanced machine control
- Meet increasing demand for higher reliability
- Open network oriented
- Realizes integrated programming support
- Applicable to software control
- Realizes remote monitoring, maintenance support, and preventive maintenance using IT
- SPH2000 integrates control and information/communication

|
| |
| Features |
|
1ms scan
Program scan time of 1ms is implemented by increased instruction processing speed/
Real number operation and high-precision positioning control have been put to practical use by dramatically improved floating-point operation speed.
| 1ms I/O refereshing |
| |
|
| • |
1024-point input/output is refreshed in 1ms |
| • |
Tact control assures a fixed I/O refresh interval. The I/O refresh cycle can be set to 1ms, 2ms, or up to 10ms, which is suitable for processing requiring strict tact time. |
| • |
The SPH300 and SPH2000 allows tact time setting in 0.5ms units with a minimum setting of 0.5ms. |
| |
|
| |
 |
| |
|
|
|
| |
| |
Controller Conforms to International Standard
|
Conforms to IEC 61131 international standard
| • |
Both the hardware and software conform to the IEC 61131 international standard to programmable controllers. |
| • |
The programming language conforms to the IEC 61131-3 international standard. |
| |
|
| Conforming to international standard |
| • |
Conforms to the CE marking, UL standards and RoHS directive (conforming one after another) as well as IEC standard. |
| • |
Conforms to the LR shipping standard (England). |
| |
|
|
|
| |
| |
Multi-CPU System Applicable to Up to 8 CPUs (SPH300/SPH2000)
|
Parallel processing with up to 8 CPUs
Alleviates the load per each CPU allowing high speed processing of a large application program.
For example, the load can be distributed for advanced processing and sequence control processing with additional CPUs. I/O refresh control is performed automatically even if parallel processing by multiple CPUs is performed.
 |
|
| |
| |
|
| |
| |
| General Specifications |
| Item |
Specification |
Physical Environment Condition |
Operating ambient temperature |
0 to +55°C |
|
| Storage temperature |
-25 to +70°C |
|
| Relative humidity |
20 to 95% RH no condensation |
|
| Pollution degree |
2 (Free from conductive dust) |
|
| Corrosion immunity |
Free from corrosive gasses, not stained with organic solvents |
|
| Operation altitude |
2000m or less above sea level
(Transport condition: 70kPa or more) |
|
| Mechanical Service Condition |
Vibration |
Half amplitude: 0.15mm, Constant acceleration: 19.6m/s² two hours in each three axes, total six hours |
|
| Shock |
Acceleration peak: 147m/s² three times in each three axes |
|
| Electrical Service Condition |
Electronic discharge |
Contact discharge: ±6kV,
Aerial discharge: ±8kV |
|
| Radiated, radio-frequency, electromagnetic field |
80 to 1,000MHz (10V/m) |
|
EFT/B
(Electrical fast transient/burst) |
±2kV (excluding the communication line) |
|
| Lightning impulse surge |
±4kV common mode, ±2kV normal mode |
|
| Conducted radio frequency |
150kHz to 80MHz, 10V |
|
| Power frequency magnetic field |
50Hz, 30A/m |
|
| Damped oscillatory wave |
±2kV, 1MHz ring waves |
|
| Square wave |
±1.5kV rise time 1ns, pulse width 1µs 50Hz |
|
| Construction |
Panel-mounting type IP30 |
|
| Cooling |
Self-cooling |
|
|
|
| |
|
| |
|
|
|